Hot Work Permit
This procedure covers welding, cutting, grinding, brazing and other spark-producing operations.
What This Procedure Covers
- Choose the method and authorize the location
For welding, cutting, brazing, grinding and other work producing ignition-capable heat or sparks. Consider a suitable cold-work method or moving the task to a designated safe area before authorizing hot work.
The permit must describe the actual work: Define the location, validity period, boundaries and conditions for this task. Confirm required inspection and authorization before starting. A permit for one location or shift is not permission to move the work or continue after conditions change.
- Inspect the surroundings and exposed areas
Inspect the work area and every place that sparks, molten material or conducted heat could reach. Include the opposite side of partitions, floors below, roof voids, penetrations and other concealed exposures.
Do not proceed where fire prevention cannot be assured: Remove combustibles where practicable and use suitable protection where authorized. Do not assume a fixed radius captures every hazard. If exposed spaces cannot be assessed or protected, stop and obtain another method. Fire watch is an additional control, not permission to work with uncontrolled hazards. Do not authorize hot work in a flammable or explosive atmosphere. Resolve impaired fire protection through the applicable site and authority process before work. Reconfirm controls when adjacent activities introduce fuels, solvents, dust or other new hazards.
- Address the workpiece and exposure hazards
Identify what the equipment or material contains or previously contained. Obtain the applicable SDS and determine hazards from coatings, residues, consumables and the process itself before work.
An empty container is not proof of a safe condition: Do not heat or cut a used container, pipe or vessel without the required specialist assessment and written preparation procedure. Confined-space entry and work on energized or pressurized equipment require separate authorization. This hot-work record does not replace those procedures. Assess fume exposure before work rather than waiting for irritation. Use effective source controls and suitable ventilation; provide appropriate respiratory protection where the assessment requires it. Outdoor work or an open door alone does not establish adequate exposure control.
- Inspect equipment and protect the crew
Use equipment suited to the process and maintained to its instructions. Check leads, holders, hoses, regulators, guards and safety devices as applicable. Remove defective equipment from service.
Protect adjacent workers as well as the operator: Position suitable welding screens and spark protection without obstructing ventilation or exits. Keep cables and hoses protected from traffic, heat and sharp edges. Maintain stable access and safe workpiece support; control hot offcuts and mark materials that remain hot. Secure cylinders and follow gas-specific handling instructions. Keep oxygen equipment free of oil and grease. Apply the relevant cylinder-storage separation requirements when cylinders are in storage; do not confuse storage rules with the approved operating arrangement.
- Maintain watch and stop for changed conditions
Assign trained fire-watch personnel and sufficient coverage for all exposed areas. Confirm communications, alarm response and relief before starting. Stop hot work if required coverage or controls are lost.
Keep the fire watch at least 60 minutes after work ends: Keep a fire watch for at least 60 minutes after work ends (company rule; the OSHA minimum is 30, 1910.252(a)(2)(iii)(B)), longer if the permit or adopted rules require it, with any further monitoring they require. Measure from the last hot-work activity. Keep watch personnel free of duties that prevent observation. Reassess authorization after breaks or changes in location, materials or conditions. For fire or smoke, stop work and activate the site emergency response without delaying alarm or escape. Only trained, authorized personnel may use extinguishing equipment when conditions and a safe escape route permit. Do not remain in an unsafe area to complete a watch.
- Close the permit and hand over
Make equipment safe under its operating instructions, inspect the exposed areas and complete the required monitoring. Record unresolved conditions and obtain the designated person's release before closing the permit.
Reference guidance: OSHA 1910.252 and 1926.350; CCOHS Hot Work; HSE welding-fume controls. Complete with adopted local requirements, the site permit program and actual equipment instructions.
Download the Full PDF Template
Get the complete Hot Work Permit document as a fillable PDF, part of the Safe Work Procedures Template Pack.
Get This SWP + 4 More Free
Choose from 112 procedures. No credit card, no commitment.
Pick Your 5 Free SWPsWant Digital Sign-Off for Your SWPs?
Make Safety Easy lets your crew acknowledge procedures on any device. Track who read what, when. No more lost paper forms.
Start Your Free Trial