Electrical Work Safety
This procedure covers work on or near electrical systems and equipment.
Scope and Purpose
This procedure sets the basic electrical rules for everyone on our sites: electricians, other trades, operators and labourers. It covers the electrical hazards met on a normal work day, and it tells you which SWP to use for higher-risk electrical tasks.
Covers:
Hazard Identification
- Shock from damaged cords, plugs or tools
- Ground fault in wet or conductive locations
- Contact with exposed live parts (open panel, missing cover, open knockout)
- Unexpected re-energization or backfeed during work
- Arc flash and arc blast when operating, opening or testing equipment
- Contact with overhead power lines (ladders, scaffold, long tools, material, equipment)
- Striking underground cables while digging or drilling
- Resetting a breaker or replacing a fuse onto a fault
- Blocked working space or blocked access to disconnects
- Conductive jewelry, ladders and long objects near live parts
- Conductive cleaning materials near live parts
- Ignition of flammable gas, vapour or dust by electrical equipment
- Fall or strike after a shock
- Fire from overloaded or damaged wiring
Required PPE
- Safety glasses.
- Hard hat. Where there is a danger of head injury from shock or burns from contact with exposed live parts, the head protection must be nonconductive; use a hard hat marked for electrical protection (US marking Class E).
- Work gloves suited to the task. Work gloves are not electrical insulation.
- Safety footwear. Do not rely on footwear as the insulation from ground.
- Dielectric footwear and voltage-rated rubber mats: extra protection where the hazard assessment calls for it. They never replace isolation, rubber gloves or insulating covers.
- Insulated protective gloves (29 CFR 1926.416(a)(2)).
- PPE as set by SWP-058 and the SWP-052 permit: arc-rated clothing and face protection at or above the label value, and rubber insulating gloves with leather protectors in the class for the voltage. Maximum use voltage (AC): Class 00 = 500 V, Class 0 = 1,000 V (29 CFR 1910.137 Table I-4). Higher classes: see SWP-052.
- Eye and face protection wherever arcs, flashes or flying parts from an electrical explosion can cause injury.
Key Procedure Steps
Plan the work
- Supervisor finds out whether any energized circuit, exposed or hidden, is where the work could bring a person, tool or machine into contact with it.
- Decide who does what.
- For any work on a circuit: plan to de-energize and lock out under SWP-001.
- Identify overhead lines.
- Before digging, drilling or driving into the ground, walls or slabs: get utilities located and marked.
Daily set-up (all workers)
- Inspect every cord set, plug and cord-connected tool before use on each shift: loose parts, bent or missing pins, damaged jacket or insulation, pinched or crushed sections.
- Check the plug and receptacle match before plugging in.
- Temporary power: plug only into GFCI-protected receptacles (company rule: GFCI on every temporary receptacle; on US construction sites an AEGCP may run as well but never replaces the GFCI).
- Route cords off walkways and away from doors, vehicles and sharp edges.
- Wet or conductive locations: use equipment approved for the location, keep hands dry when plugging and unplugging, and handle wet energized connections only with insulating protective equipment.
- Keep the working space in front of panels and the path to every switch clear.
Working near electrical equipment
- Keep panel covers, doors and dead fronts closed.
- Remove or cover conductive jewelry.
- Do not clean, sweep or wash close to live parts without barriers.
- Do not use electrical equipment that can ignite flammable gas, vapour or dust where it may be present, unless measures are taken to stop a hazardous atmosphere forming.
- If a breaker trips or a fuse blows: do not reset it or replace the fuse until a qualified person has determined the circuit and equipment can be safely re-energized.
Work on circuits and equipment (qualified workers only)
- Follow SWP-001: identify all sources (including generators, UPS, PV, batteries and capacitors); open the disconnecting means (not a push button or interlock); release stored energy; apply your own lock and tag to each disconnecting means.
- Test before touch.
- Canada federal: if the equipment is not live but can become live, either use live-work procedures or connect a safety ground (COHSR 8.5(3)).
- If anything must stay live, or a nearby part cannot be isolated, stop and use SWP-052.
- Do not defeat an interlock unless you are qualified, working under SWP-052, and you restore it when the task is done.
Close-out and re-energizing
- Qualified person checks that tools, jumpers, shorts and temporary grounds are removed and covers are back on.
- Warn everyone exposed to stay clear.
- Each lock and tag is removed by the person who put it on (absent-worker removal only under SWP-001).
- Confirm visually that everyone is clear.
- Leave the area tidy, cords coiled, damaged items tagged, and report any defects found.
Each step is shortened to its first sentence. The full procedure, with every condition, checklist and sign-off field, is in the PDF.
Training Requirements
- All workers exposed to electrical hazards: This SWP. The electrical safe work practices that apply to their job: cord and tool inspection, GFCI use, wet locations, keeping out of barricaded areas, overhead and underground lines, reporting (29 CFR 1910.332(b)(1), (2)).
- Qualified worker: Trade qualification for the equipment and voltage.
- Supervisor: This SWP, SWP-001, how to find energized circuits before work, how to read arc flash labels, when SWP-052 is required, stop-work authority.
- AEGCP competent person (US construction, where used): The written AEGCP, the test methods and records (29 CFR 1926.404(b)(1)(iii)(B)).
Regulatory References
- 29 CFR 1910.331 to 1910.335 (Subpart S electrical safety-related work practices): 1910.332 Training, 1910.333 Selection and use of work practices, 1910.334 Use of equipment, 1910.335 Safeguards for personnel protection
- 29 CFR 1910.303 (general electrical requirements, working space and guarding); 1910.399 (definitions)
- 29 CFR 1910.137 (electrical protective equipment)
- 29 CFR 1910.147 (lockout/tagout; scope excludes construction and Subpart S electrical work)
- 29 CFR 1926.402 to 1926.405 (construction electrical installations), incl. 1926.404(b)(1) GFCI and assured equipment grounding conductor program
- 29 CFR 1926.416, 1926.417 (construction electrical work practices and tagging)
- 29 CFR 1904.39 (reporting to OSHA)
- Canada Labour Code Part II, incl. s.125(1)(q) (training) and s.128 (refusal to work)
- Canada Occupational Health and Safety Regulations SOR/86-304, Part VIII Electrical Safety (ss.8.1 to 8.23 and Schedule), Part XII Protection Equipment, Part XV Hazardous Occurrence Investigation, Recording and Reporting
- Provinces and territories have their own OHS regulations; check the one that applies to the work site.
Download the Full PDF Template
Get the complete Electrical Work Safety document as a fillable PDF, part of the Safe Work Procedures Template Pack.
Get This SWP + 4 More Free
Choose from 112 procedures. No credit card, no commitment.
Pick Your 5 Free SWPsWant Digital Sign-Off for Your SWPs?
Make Safety Easy lets your crew acknowledge procedures on any device. Track who read what, when. No more lost paper forms.
Start Your Free Trial