Temporary Electrical Installations

Installation, inspection and maintenance of temporary electrical wiring on construction sites.

Revision 2.1 Updated Jun 19, 2026

Scope and Purpose

This procedure covers setting up, using, inspecting, changing and removing temporary power and lighting on construction sites and during maintenance, remodeling or repair work. This includes temporary service poles and panels, portable distribution boxes (spider boxes), portable and vehicle-mounted generators, extension cords, temporary lighting strings and cord-and-plug tools.

Temporary wiring is still wiring. Except where the temporary-wiring rules allow less, it must meet the same rules as permanent wiring (29 CFR 1926.405(a)(2)(i); 1910.305(a)(2)).

Hazard Identification

  • Shock from a ground fault in a tool or cord, worse in wet conditions
  • Damaged cords and plugs (cut jacket, crushed cord, missing or bent pins, exposed conductors)
  • Broken ground path (ground pin cut off, two-prong adapters, two-wire cords)
  • Contact with live parts in panels, spider boxes and boxes (missing covers, open knockouts, blanks missing)
  • Overloaded circuits, overheating, fire
  • Arc flash or blast when operating or working in temporary panels
  • Contact with temporary overhead conductors by equipment, ladders, scaffolds, long material
  • Wet and conductive locations (tanks, drums, vessels, standing water, rain)
  • Broken lamps and hot bulbs
  • Trips and falls over cords
  • Generator hazards (carbon monoxide, backfeed into building wiring, poor bonding)
  • Ignition of flammable vapour or dust by cords, tools or lights
  • Repeated resetting of tripped breakers or GFCIs

Required PPE

  • Hard hat, Class E (electrical) where overhead temporary wiring or lights are present.
  • Safety glasses.
  • Safety footwear. Do not rely on boots as insulation from ground.
  • Work gloves suited to the task. Rubber insulating gloves are not a substitute for de-energizing.
  • High-visibility clothing per site rules.

Key Procedure Steps

Set-up (qualified person)

  1. Plan the layout: power source, feeder routes, panel and spider box locations, cord routes.
  2. Use only listed, labelled equipment, installed per its listing and instructions (1926.403(a), (b)(2)).
  3. Start feeders at a distribution center.
  4. Start branch circuits at a panel or power outlet.
  5. Use grounding-type receptacles with an equipment grounding conductor on every branch circuit.
  6. Provide a disconnect or plug connector that cuts all ungrounded conductors of each temporary circuit, and label every circuit at its breaker or disconnect (1926.405(a)(2)(ii)(D); 1926.403(h)).
  7. GFCI (company rule, all sites): put GFCI protection on every temporary receptacle outlet workers use, including 120 V single-phase 15, 20 and 30 A outlets, other temporary receptacles, cord connectors and generator receptacles.
  8. Mount enclosures in wet and damp locations so water cannot enter or collect; use weatherproof enclosures in wet locations (1926.405(e)).
  9. Close every unused opening in boxes and cabinets; put covers on every box (1926.405(b)(1)-(2)).
  10. Guard live parts of 50 V or more by enclosures or location (1926.403(i)(2)).
  11. Keep working space in front of panels clear: at least 3 ft (0.9 m) deep for 0-150 V to ground, and 3 to 4 ft (0.9 to 1.2 m) for 151-600 V depending on what is on the opposite side (Table K-1); at least 30 in (762 mm) wide; headroom at least 6 ft 3 in (1.91 m) at panels; never used for storage (1926.403(i)(1)).
  12. Overhead outdoor open conductors (600 V or less), minimum clearance: 10 ft (3.05 m) above grade, sidewalks or any platform they could be reached from; 12 ft (3.66 m) over vehicle traffic other than trucks; 15 ft (4.57 m) over truck traffic; 18 ft (5.49 m) over public streets, alleys, roads and driveways; 3 ft (914 mm) from windows, doors and fire escapes (1926.404(c)(1)(ii)-(iii)).
  13. Temporary lighting: lamps guarded against contact and breakage; metal-case sockets grounded; lights not hung by their cords unless designed for it (1926.405(a)(2)(ii)(E)-(F)).
  14. Generators: follow the manufacturer's grounding and bonding instructions.
  15. Test GFCIs and polarity before handing the system over.

Use (all workers)

  1. Before each shift, inspect every cord, plug, connector and tool you will use: jacket, pins, strain relief, housing (1910.334(a)(2); 1926.416(e)(1)).
  2. Press the GFCI test button before the first use each day; it must trip.
  3. Use only three-wire extension cords designed for hard or extra-hard usage (1926.405(a)(2)(ii)(J)).
  4. Plug and unplug with dry hands.
  5. Do not raise or lower tools or equipment by their cords.
  6. Keep cords out of walkways and work spaces (1926.416(b)(2)).
  7. No daisy-chained cords or power strips (company rule).
  8. Do not open panels or spider boxes, change breakers, or remove covers.
  9. If a GFCI or breaker trips: unplug the load, inspect the cord and tool, and reset only after the faulty item is found and removed.
  10. Do not use ordinary electrical tools, cords or lights where flammable gas, vapour or dust may be present (1910.334(d)).

Changes and close-out (qualified person)

  1. Before adding, moving or removing circuits, de-energize and lock out (SWP-001; 1926.417: deactivated controls tagged, circuits rendered inoperative and tagged at every point they can be energized).
  2. After flooding, water entry into enclosures, a vehicle running over cords, fire, or other damage: de-energize, inspect and test the affected wiring before re-energizing.
  3. Remove temporary wiring immediately when the construction or purpose it served is complete (1926.405(a)(2)(i); 1910.305(a)(2)(ii)).
  4. Inspect returned cords and tools; tag and remove damaged ones.

Each step is shortened to its first sentence. The full procedure, with every condition, checklist and sign-off field, is in the PDF.

Training Requirements

  • Qualified person (installs, changes, repairs, tests): Familiar with the construction and operation of the equipment and its hazards (1926.449).
  • Competent person for the AEGCP (if used): Designated in writing; trained in the program, the tests, the test equipment and the record (1926.404(b)(1)(iii)(B)).
  • Supervisor: This SWP; the daily walk; how to spot damaged equipment and missing protection; when to call the qualified person.
  • All workers using temporary power: Cord and tool inspection, GFCI test, what to do when a GFCI trips, what not to touch, how to report.

Regulatory References

  • 29 CFR 1926 Subpart K: 1926.403 General requirements; 1926.404 Wiring design and protection (incl. (b)(1) GFCI and AEGCP, (c) outdoor clearances, (f) grounding); 1926.405 Wiring methods (incl. (a)(2) temporary wiring, (g) flexible cords); 1926.416 Safety-related work practices; 1926.417 Lockout and tagging of circuits; 1926.449 Definitions.
  • 29 CFR 1910 Subpart S (general industry): 1910.304(b)(3) GFCI for personnel; 1910.305(a)(2) Temporary wiring; 1910.332 Training; 1910.334 Use of equipment.
  • 29 CFR 1904.39 Reporting fatalities, hospitalizations, amputations and losses of an eye.
  • Canada Labour Code Part II, incl. s.128 (refusal to work).
  • Canada Occupational Health and Safety Regulations SOR/86-304, Part VIII Electrical Safety (incl. 8.3 Canadian Electrical Code, 8.4 qualified person); Part XV Hazardous Occurrence Investigation, Recording and Reporting.
  • Provinces and territories have their own OHS regulations and adopt their own edition of the electrical code; check the one that applies to the work site.

Download the Full PDF Template

Get the complete Temporary Electrical Installations document as a fillable PDF, part of the Safe Work Procedures Template Pack.

Get Template Pack

Get This SWP + 4 More Free

Choose from 112 procedures. No credit card, no commitment.

Pick Your 5 Free SWPs

Want Digital Sign-Off for Your SWPs?

Make Safety Easy lets your crew acknowledge procedures on any device. Track who read what, when. No more lost paper forms.

Start Your Free Trial