Spill Response and Cleanup
Chemical and petroleum spill response, containment, cleanup and regulatory reporting procedures.
Scope and Purpose
This procedure covers what workers do when fuel, oil, hydraulic fluid, chemicals or other hazardous materials leak or spill: protecting people, deciding whether the spill is one the crew can safely handle, containing and cleaning up small spills, calling responders for the rest, disposing of the waste, and reporting.
Only clean up a spill if you know what it is, you have read the SDS, you have the right PPE and kit, and it can be controlled from where you are. If any of these is missing, get out, keep others out, and call for help.
Hazard Identification
- Fire or explosion from flammable liquids or vapours
- Breathing vapours, mists or dust
- Skin and eye contact (corrosives, solvents, fuel)
- Mixing incompatible chemicals
- Oxygen-deficient or toxic air in low or enclosed areas (pits, trenches, sumps, vessels' holds)
- Spill reaching drains, ditches, soil or water
- Slips on spilled liquid
- Lifting full drums and bags
- Working near water (wharf, barge)
- Unknown material
Required PPE
- Chemical-resistant gloves of a material the SDS lists for that substance.
- Splash goggles; face shield over goggles for corrosives or splashing.
- Chemical-resistant coveralls or apron and boots (or boot covers) where liquid may reach clothing.
- Site PPE: hard hat, high-visibility apparel, safety footwear.
- Life jacket or PFD on wharves, barges and near water (SWP-109).
- Only where the SDS or air checks call for one, and only for workers in the respiratory protection program: medically evaluated and fit-tested before first use, when the facepiece changes, and at least annually (US 1910.134(e), (f)(2), applied to construction by 1926.103; Canada federal COHSR 12.13, CSA Z94.4).
- Emergency response with an inhalation hazard: positive-pressure self-contained breathing apparatus until the incident commander decides from air monitoring that a lower level is safe (1910.120(q)(3)(iv)). Crews who are not trained for this do not enter; they evacuate.
Key Procedure Steps
Stop, warn, identify
- Stop work nearby.
- Identify the material from the container label, SDS, placard or the person who was using it.
- If anyone is hurt or splashed: get them out of the area if safe, flush skin or eyes with water at once (SWP-090) and call 911.
Decide: incidental or emergency
- It is an emergency if any of these is true.
Emergency spill
- Evacuate the area.
- Call 911 and the site emergency contact.
- Keep everyone out.
- Only trained responders act, at their level (Section 6).
Incidental spill
- Stop the flow if a simple action from where you stand will do it: stand a tipped container upright, close a valve, shut off a pump or engine.
- Put on PPE from the SDS (Section 5).
- Flammable material: shut off ignition sources and engines nearby.
- Protect drains first: cover storm drains and block ditches in the spill's path.
- Contain: put socks, booms or a berm around the spill.
- Absorb from the outside edge inward.
- Powders and solids: dampen or use a HEPA vacuum; no dry sweeping that raises dust.
- Pick up used absorbent, contaminated soil and disposable PPE with non-sparking tools.
- Clean the surface with the method the SDS gives.
- Decontaminate tools and reusable PPE. Wash hands and face before eating, drinking or smoking.
Waste and close-out
- The environmental coordinator decides whether the waste is hazardous waste and arranges a licensed carrier and disposal.
- Restock the spill kit the same shift.
- Record the spill: date, time, place, material, estimated amount, cause, who responded, actions, where the waste went, reports made, and steps to stop it happening again.
- Fix the cause (leaking hose, poor storage, missing containment) before the work restarts.
Each step is shortened to its first sentence. The full procedure, with every condition, checklist and sign-off field, is in the PDF.
Training Requirements
- All workers: Hazard communication / WHMIS for the materials they use, incl.
- Incidental spill responders (crew members who clean up incidental spills): The above, plus the SDS for each material, PPE selection, use of the spill kit, waste bagging and labelling (company rule).
- On-site emergency team, operations level (only where the site chose this model): At least 8 hours of training or shown competency in the operations-level topics, certified by the employer (1910.120(q)(6)(ii); 1926.65(q)(6)(ii)).
- Hazardous materials technician (stops the release at the source): At least 24 hours of training equal to operations level, plus technician competencies, certified by the employer (1910.120(q)(6)(iii)).
- On-scene incident commander (employer's own): At least 24 hours of training equal to operations level, plus incident command competencies (1910.120(q)(6)(v)).
- Oil-handling personnel at a site with an SPCC Plan: Training in equipment operation and maintenance to prevent discharges, discharge procedures, pollution rules and the SPCC Plan (40 CFR 112.7(f)(1)).
- Environmental coordinator: Reporting rules for the site (Section 9), waste classification and records.
Regulatory References
- 29 CFR 1910.120 and 1926.65, Hazardous waste operations and emergency response (definitions; (q) emergency response).
- 29 CFR 1910.38, Emergency action plans.
- 29 CFR 1910.1200 (applied to construction by 1926.59), Hazard communication.
- 29 CFR 1910.134 (applied to construction by 1926.103), Respiratory protection.
- 29 CFR 1926.21(b) (training); 1904.39 (reporting).
- 40 CFR 302 (CERCLA designation, reportable quantities and notification: 302.3, 302.4, 302.5, 302.6).
- 40 CFR 110 (discharge of oil: 110.3, 110.6).
- 40 CFR 112 (Spill Prevention, Control, and Countermeasure: 112.1, 112.4, 112.7).
- 40 CFR 355 (EPCRA emergency release notification: 355.30, 355.40, 355.42).
- 40 CFR 262 (hazardous waste generators, 262.40 records); RCRA 40 CFR 260 to 265 (named).
- COHSR SOR/86-304: Part X (10.4, 10.13, 10.14, 10.15, 10.20, 10.28, 10.34), Part XII (12.12, 12.13), Part XV (15.5, 15.8), Part XVII (17.5, 17.6), Part XIX (19.6).
- Fisheries Act, s. 38(4) to (7); Deposit Out of the Normal Course of Events Notification Regulations (SOR/2011-91).
- Named only: Canadian Environmental Protection Act, 1999 and Environmental Emergency Regulations, 2019; Canada Shipping Act, 2001; Transportation of Dangerous Goods Regulations.
- Provincially regulated work and provincial spill reporting rules: follow your province.
Download the Full PDF Template
Get the complete Spill Response and Cleanup document as a fillable PDF, part of the Safe Work Procedures Template Pack.
Get This SWP + 4 More Free
Choose from 112 procedures. No credit card, no commitment.
Pick Your 5 Free SWPsWant Digital Sign-Off for Your SWPs?
Make Safety Easy lets your crew acknowledge procedures on any device. Track who read what, when. No more lost paper forms.
Start Your Free Trial