Underground cable and utility locating procedures with electromagnetic, GPR and potholing methods.

Rev 02 Updated Apr 19, 2026

What This Procedure Covers

  1. Define the survey and responsibilities

    For trained locators investigating buried services before ground disturbance. A locator survey supports the excavation plan; it is not a certificate that the ground is free of services. Apply local notification, marking and renewal requirements and the instrument instructions.

    Reconcile the records with what is on site: Review available plans, owner information and previous surveys, then walk the area for cabinets, meters, covers, service entries and other clues. Record contradictions and inaccessible areas. Do not treat an absent mark or an old abandoned-service label as proof that a facility is absent or safe.

  2. Prepare instruments and a safe survey method

    Check equipment condition, batteries, function checks and any calibration requirements before use. Establish pedestrian and traffic controls. Opening utility enclosures, entering chambers or making electrical connections needs separate authority and controls.

    Do not connect to an unknown or live conductor: Choose signal application under the equipment manual and owner authorization. Direct connection to a live conductor can be fatal and requires a qualified person (US 29 CFR 1910.399; Canada federal COHSR 1.2; see SWP-052) and purpose-designed equipment under a separate electrical work procedure. This survey record does not authorize it. Protect others from transmitter leads and terminals. An electromagnetic locator can miss live cables and may combine nearby services into one response. Power mode alone cannot establish that the area is clear. Check for coupled signals and interference, and record uncertainty instead of selecting the most convenient trace. Follow the instrument method for validating depth indications.

  3. Trace and assess the limitations

    Trace services through the full survey area using appropriate complementary modes and methods. Non-metallic facilities may need tracer wires, approved sondes or another investigation method; these arrangements can also fail or be incomplete.

    GPR does not guarantee detection of every utility: Ground-penetrating radar performance depends on ground conditions, target properties and the survey setup. Conductive wet or clay-rich ground can severely limit penetration; metal can obscure features beneath it. Record usable coverage and interpretation limits. An absent reflection is not evidence that a utility is absent. Keep instrument-derived depth estimates distinct from physically verified measurements. Resolve unexpected or missing facilities with the owner and further investigation. Do not infer that a line has constant depth or follows the shortest route between known points.

  4. Mark, verify and brief the excavation crew

    Use the local marking convention, owner identification and clearly referenced offsets where needed. Avoid driving stakes or pins that could strike shallow services. Maintain a dated sketch and photographs, including survey boundaries and unresolved areas.

    An estimated trace is not an excavation release: Use the separate utility-exposure procedure to confirm position by safe, approved means before excavation approaches the service. Apply the actual tolerance-zone rule and owner restrictions. Record confirmed identity, position, depth and limitations; do not remove a restriction simply because a locator displayed a depth. Stop affected work when marks are lost, the scope changes or unexpected services appear. Request updated information or re-marking through the proper process. Ticket validity and renewal periods vary; use the local requirement rather than a universal 14-day rule.

  5. Close the survey and retain the evidence

    Retain the ticket, responses, plans, instrument records, survey data, photos and verification results together. Identify who must resolve each open issue and who can release the affected work. Review the survey when site conditions or the proposed disturbance changes.

Reference guidance: HSE HSG47; Radiodetection RD8200 manual and Frequencies support; USDA NRCS GPR guidance; FHWA underground utility GPR guidance; OSHA 1926.651(b); local one-call instructions. Use the exact instrument manual and local rules.

Download the Full PDF Template

Get the complete Underground Cable Locating document as a fillable PDF, part of the Safe Work Procedures Template Pack.

Get Template Pack

Get This SWP + 4 More Free

Choose from 112 procedures. No credit card, no commitment.

Pick Your 5 Free SWPs

Want Digital Sign-Off for Your SWPs?

Make Safety Easy lets your crew acknowledge procedures on any device. Track who read what, when. No more lost paper forms.

Start Your Free Trial