Waterproofing and Membrane
Waterproofing membrane application including hot-apply, torch-applied and cold-applied systems.
What This Procedure Covers
- Select the approved system
For installation of the specified waterproofing system. Identify every primer, adhesive, membrane, coating and cleaner. Cold-applied, self-adhered, hot-applied and torch-applied systems do not share one universal method.
Assess a lower-risk method first: Consider a compatible system that avoids flame or hazardous solvents. Product substitution must preserve the specified assembly and manufacturer compatibility. Low-VOC, water-based or solvent-free does not mean free of all chemical hazards.
- Access, support and nearby occupants
Confirm safe access and the work platform, edge and opening protection, substrate capacity and material storage. Below-grade or enclosed work requires its own access and atmosphere assessment before entry.
Protect the surrounding building: Identify air intakes, occupied areas, penetrations and concealed combustible construction. Agree on isolation and occupant protection with the building representative. Do not begin if vapour, overspray or heat could enter an uncontrolled area. Provide safe walking routes and collect release liners and offcuts as work proceeds. Do not spread improvised traction material onto a membrane unless the system manufacturer permits it.
- Control chemical exposure
Assess the exact products, quantities, work duration and method. Spraying can produce substantially different exposure from brushing or rolling. Review other hazardous ingredients as well as solvent content.
Keep controls in place through clearance: Maintain segregation and ventilation until the assessed risk has cleared. Do not use odour, surface dryness or a flammability reading alone as proof the air is safe to breathe. Re-entry criteria must address the actual product and work conditions. Select respiratory protection for the substance and application, with required training and fit testing. Do not prescribe one organic-vapour cartridge for every coating. Keep chemicals off skin and never clean skin with solvent.
- Authorize heat or flame separately
Complete the hot-work assessment before any torch or kettle work. Confirm the approved assembly and flame-free areas, permits, trained applicators, fire protection and access to concealed spaces for inspection.
Specify the fire watch before starting: Assign a dedicated competent fire watcher and record coverage during work, interruptions and after completion. Keep a fire watch for at least 60 minutes after work ends (company rule; the OSHA minimum is 30). After torch-applied roofing, keep it for at least two hours (NRCA/MRCA CERTA). Apply any longer period required by the applicable code, permit, insurer or site plan. Use the product and equipment limits for hot material and heating; do not assume a generic temperature or equiviscous-temperature value is the maximum safe limit. Confirm extinguishers, spill and burn response arrangements before authorization.
- Apply and verify the system
Follow the approved product method for preparation, mixing, application, joints and curing. Record site conditions and hold points. Do not add unapproved thinner or change component ratios to make application easier.
Stop when conditions leave the approved method: Stop for loss of ventilation, damaged equipment, uncontrolled ignition sources, unsafe access or conditions outside the product limits. Record the issue and obtain authorization before restarting. Keep non-essential people clear of uncured material and application equipment. Use the required inspection or test method without damaging the assembly or overloading the structure. Flood testing and other specialist tests need an approved plan covering load, drainage and occupied areas.
- Clean up, hand over and review
Collect containers, liners, contaminated materials and cleaning waste using the SDS and local disposal requirements. Secure remaining products. Close permits only after their inspection and monitoring conditions have been met.
Reference guidance: HSE construction solvents and coatings; NRCA/MRCA CERTA torch-safety guidance; NFRC Safe2Torch. Product technical sheets, SDS and applicable local requirements govern the completed installation method.
Download the Full PDF Template
Get the complete Waterproofing and Membrane document as a fillable PDF, part of the Safe Work Procedures Template Pack.